NotesNotes on operation | the blocks can be bridged with one another via the conductor shaft, for corresponding plug-in bridges, see accessories |
General |
Note | The maximum load current of a single clamping unit must not be exceeded. |
| For power distribution applications, IEC 60364-4-43.2008; modified + corrigendum Okt. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff must be observed! |
Product propertiesProduct type | Distributor terminal block |
Number of connections | 19 |
Number of rows | 1 |
Potentials | 1 |
Insulation characteristics |
Overvoltage category | III |
Degree of pollution | 3 |
Electrical propertiesRated surge voltage | 8 kV |
Maximum power dissipation for nominal condition | 0.77 W |
Connection dataService Entrance | yes |
Number of connections per level | 19 |
Nominal cross section | 2.5 mm² |
Rated cross section AWG | 14 |
Load contact |
Stripping length | 8 mm ... 10 mm |
Internal cylindrical gage | A3 |
Conductor cross section solid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section, flexible [AWG] | 26 ... 14 |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Nominal current | 24 A |
Maximum load current | 32 A (with 4 mm² conductor cross section) |
Maximum total current | 57 A (with 10 mm² conductor cross section) |
Nominal voltage | 690 V |
Line contact |
Stripping length | 10 mm ... 12 mm |
Conductor cross section solid | 0.5 mm² ... 10 mm² |
Cross section AWG | 20 ... 8 |
Conductor cross section flexible | 0.5 mm² ... 10 mm² |
Conductor cross section, flexible [AWG] | 20 ... 10 |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) | 0.5 mm² ... 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 6 mm² |
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² ... 1.5 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 1.5 mm² |
Nominal current | 41 A (with 6 mm² conductor cross section) |
Maximum load current | 57 A (with 10 mm² conductor cross section) |
Nominal cross section | 6 mm² |
Load contact Connection cross sections directly pluggable |
Conductor cross section solid | 0.34 mm² ... 4 mm² |
Conductor cross section, solid [AWG] | 24 ... 12 |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) | 0.34 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.34 mm² ... 2.5 mm² |
Line contact Connection cross sections directly pluggable |
Conductor cross section solid | 1 mm² ... 10 mm² |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) | 1 mm² ... 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 1 mm² ... 6 mm² |
DimensionsWidth | 56.5 mm |
Height NS 35/7,5 | 30.9 mm |
Length | 45.7 mm |
Material specificationsColor | gray |
Flammability rating according to UL 94 | V0 |
Insulating material group | I |
Insulating material | PA |
Static insulating material application in cold | -60 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Electrical testsSurge voltage test |
Test voltage setpoint | 9.8 kV |
Result | Test passed |
Temperature-rise test |
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Result | Test passed |
Short-time withstand current 6 mm² | 0.72 kA |
Short-time withstand current 10 mm² | 1.2 kA |
Result | Test passed |
Power-frequency withstand voltage |
Test voltage setpoint | 1.89 kV |
Result | Test passed |
Mechanical propertiesMechanical data |
Open side panel | No |
Mechanical testsMechanical strength |
Result | Test passed |
Attachment on the carrier |
DIN rail/fixing support | NS 35 |
Test force setpoint | 5 N |
Result | Test passed |
Note | When aligning several blocks, it is recommended to either place a DIN rail adapter underneath the connection point or a flange element between the blocks. |
| For versions with 6 or 7 connections, it is enough to place one DIN rail adapter centrally per block and place flange elements after every other block. |
| When using the DIN rail adapter PTFIX-NS35, an aligned block must not protrude by more than a half. |
Test for conductor damage and slackening |
Rotation speed | 10 rpm |
Revolutions | 135 |
Conductor cross section/weight | 0.5 mm² / 0.3 kg |
| 6 mm² / 1.4 kg |
| 10 mm² / 2 kg |
Result | Test passed |
Test for conductor damage and slackening |
Rotation speed | 10 rpm |
Revolutions | 135 |
Conductor cross section/weight | 0.14 mm² / 0.2 kg |
| 2.5 mm² / 0.7 kg |
| 4 mm² / 0.9 kg |
Result | Test passed |
Environmental and real-life conditionsAging |
Temperature cycles | 192 |
Result | Test passed |
Needle-flame test |
Time of exposure | 30 s |
Result | Test passed |
Oscillation/broadband noise |
Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Spectrum | Service life test category 2, bogie-mounted |
Frequency | f1 = 5 Hz to f2 = 250 Hz |
ASD level | 6.12 (m/s²)²/Hz |
Acceleration | 3.12g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Result | Test passed |
Shocks |
Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Pulse shape | Half-sine |
Acceleration | 30g |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Result | Test passed |
Ambient conditions |
Ambient temperature (operation) | -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Standards and regulationsConnection in acc. with standard | IEC 60947-7-1 |
| IEC 60947-7-1 |
| IEC 60947-7-1 |
| IEC 60947-7-1 |
MountingMounting type | NS 35/7,5 |
| NS 35/15 |