Phoenix VAL-SEC-T2-3S-350-FM Type 2 SPD 3P
€326.93
€265.80
Details
Product propertiesIEC test classification | II |
| T2 |
EN type | T2 |
IEC power supply system | TN-S |
| TT |
Type | DIN rail module, two-section, divisible |
Product type | Surge arrester |
Number of positions | 4 |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics |
Overvoltage category | III |
Pollution degree | 2 |
Electrical propertiesNominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling |
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating voltage | 5 V AC ... 250 V AC |
| 125 V DC (200 mA DC) |
Operating current | 5 mA AC ... 1 A AC |
| 1 A DC (30 V DC) |
Connection dataConnection method | Screw connection |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 16 mm |
Conductor cross section flexible | 2.5 mm² ... 16 mm² |
Conductor cross section solid | 2.5 mm² ... 25 mm² |
Conductor cross section AWG | 12 ... 4 |
Connection method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 6 mm² |
DimensionsWidth | 49.2 mm |
Height | 97.9 mm |
Depth | 74.5 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 2.7 Div. |
Material specificationsColor | light grey RAL 7035 |
| traffic grey A RAL 7042 |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA6.6-FR 20% GF |
| PBT-FR |
Material group | I |
Housing material | PA 6.6-FR 20 % GF |
| PBT-FR |
Protective circuitMode of protection | L-N |
| L-PE |
| N-PE |
Direction of action | 3L-N & N-PE |
Nominal voltage UN | 240/415 V AC (TN-S) |
| 240/415 V AC (TT) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC (L-N) | 350 V AC |
Maximum continuous operating voltage UC (L-PE) | 350 V AC |
Maximum continuous operating voltage UC (N-PE) | 264 V AC |
Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
| 63 A (TWIN ferrule 2 x 10 mm²) |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Follow current interrupt rating Ifi (N-PE) | 100 A (264 V AC) |
Short-circuit current rating ISCCR | 25 kA (for a backup fuse of up to 315 A gG) |
| 50 kA (for a backup fuse of up to 200 A gG) |
Voltage protection level Up (L-N) | ≤ 1.5 kV |
Voltage protection level Up (L-PE) | ≤ 1.9 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Residual voltage Ures (L-N) | ≤ 1.5 kV (at In) |
| ≤ 1.3 kV (at 10 kA) |
| ≤ 1.2 kV (at 5 kA) |
| ≤ 1.1 kV (at 4 kA) |
| ≤ 1 kV (at 2 kA) |
Residual voltage Ures (L-PE) | ≤ 1.9 kV (at In) |
| ≤ 1.5 kV (at 10 kA) |
| ≤ 1.4 kV (at 5 kA) |
| ≤ 1.3 kV (at 4 kA) |
| ≤ 1.2 kV (at 2 kA) |
Residual voltage Ures (N-PE) | ≤ 0.5 kV (at In) |
| ≤ 0.5 kV (at 10 kA) |
| ≤ 0.5 kV (at 5 kA) |
| ≤ 0.5 kV (at 4 kA) |
| ≤ 0.5 kV (at 2 kA) |
TOV behavior at UT (L-N) | 415 V AC (5 s / withstand mode) |
| 457 V AC (120 min / safe failure mode) |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 100 ns |
Response time tA (N-PE) | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
| 63 A (gG / TWIN ferrule 2x 10mm²) |
Max. backup fuse with branch wiring | 315 A (gG) |
Environmental and real-life conditionsAmbient conditions |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Approval dataUL specifications |
Maximum continuous operating voltage MCOV (L-L) | 700 V AC |
Maximum continuous operating voltage MCOV (L-N) | 350 V AC |
Maximum continuous operating voltage MCOV (L-G) | 350 V AC |
Maximum continuous operating voltage MCOV (N-G) | 264 V AC |
Nominal discharge current In (L-L) | 20 kA |
Nominal discharge current In (L-N) | 20 kA |
Nominal discharge current In (L-G) | 20 kA |
Nominal discharge current In (N-G) | 20 kA |
Mode of protection | L-L |
| L-N |
| L-G |
| N-G |
Nominal voltage | 240/415 V AC |
Power distribution system | Wye |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-L) | 3280 V |
Measured limiting voltage MLV (L-N) | 2000 V |
Measured limiting voltage MLV (L-G) | 2080 V |
Measured limiting voltage MLV (N-G) | 950 V |
Follow current (L-G) | 200 A (264 V AC) |
SPD Type | 4CA |
AC operating voltage | 125 V AC |
AC operating current | 1 A AC |
UL connection data |
Tightening torque | 40 lbf-in. ... 50 lbf-in. |
Conductor cross section AWG | 14 ... 2 (solid) |
| 14 ... 4 (flexible) |
Standards and regulationsStandards/specifications | IEC 61643-11 |
Standards/specifications | EN 61643-11 |
MountingMounting type | DIN rail: 35 mm |