Phoenix UT 4Sq Terminal Block

180 In stock
SKU
3044102
Quick Overview
Feed-through terminal block, nom. voltage: 1000 V, nominal current: 32 A, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2 - 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray
€0.77 €0.63

Shipping Information

Free Shipping - On Orders Over €150.

Money Back Guarantee.

Ships Items Quickly.

Product properties
Product typeFeed-through terminal block
Area of applicationRailway industry
Machine building
Plant engineering
Process industry
Number of connections2
Number of rows1
Potentials1
Insulation characteristics
Overvoltage categoryIII
Degree of pollution3
Electrical properties
Rated surge voltage8 kV
Maximum power dissipation for nominal condition1.02 W
Connection data
Number of connections per level2
Nominal cross section4 mm²
Level 1 above 1 below 1
Screw threadM3
Tightening torque0.6 ... 0.8 Nm
Stripping length9 mm
Internal cylindrical gageA4
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid0.14 mm² ... 6 mm²
Cross section AWG26 ... 10
Conductor cross section flexible0.14 mm² ... 6 mm²
Conductor cross section, flexible [AWG]26 ... 10
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 4 mm²
2 conductors with same cross section, solid0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve0.14 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 2.5 mm²
Nominal current32 A (with 4 mm² conductor cross section)
Maximum load current41 A (with 6 mm² conductor cross section)
Nominal voltage1000 V
NoteNote: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Nominal cross section4 mm²
Ex data
Rated data (ATEX/IECEx)
ATEX certificateKEMA 04 ATEX 2048 U
IEC Ex certificateIECEx  KEM 06.0027 U
IdentificationEx eb IIC Gb
Operating temperature range-60 °C ... 110 °C
Ex-certified accessories3047028 D-UT 2,5/10
3047167 ATP-UT
1205053 SZS 0,6X3,5
3022276 CLIPFIX 35-5
3022218 CLIPFIX 35
Plug-in bridge / FBS 2-6 / 3030336
Plug-in bridge / FBS 3-6 / 3030242
Plug-in bridge / FBS 4-6 / 3030255
Plug-in bridge / FBS 5-6 / 3030349
Plug-in bridge / FBS 10-6 / 3030271
Plug-in bridge / FBS 20-6 / 3030365
Plug-in bridge / FBS 50-6 / 3032224
Bridge data27 A / 4 mm²
Ex temperature increase40 K (33.3 A / 4 mm²)
Rated voltage630 V
for bridging with bridge690 V
- At bridging between non-adjacent terminal blocks352 V
- At bridging between non-adjacent terminal blocks via PE terminal block275 V
- At cut-to-length bridging with cover220 V
- At cut-to-length bridging with partition plate275 V
Rated insulation voltage630 V
Ex level General
Rated current30 A
Maximum load current38 A
Contact resistance0.26 mΩ
Ex connection data General
Torque range0.6 Nm ... 0.8 Nm
Nominal cross section4 mm²
Rated cross section AWG12
Connection capacity rigid0.14 mm² ... 6 mm²
Connection capacity AWG26 ... 10
Connection capacity flexible0.14 mm² ... 4 mm²
Connection capacity AWG26 ... 12
2 conductors with same cross section, solid0.14 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG rigid26 ... 16
2 conductors with same cross section, stranded0.14 mm² ... 1.5 mm²
2 conductors with the same cross-section AWG flexible26 ... 16
Dimensions
Width6.2 mm
End cover width2.2 mm
Height46.9 mm
Height NS 35/1555 mm
Height NS 35/7,547.5 mm
Length47.7 mm
Material specifications
Colorgray
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Electrical tests
Surge voltage test
Test voltage setpoint9.8 kV
ResultTest passed
Temperature-rise test
Requirement temperature-rise testIncrease in temperature ≤ 45 K
ResultTest passed
Short-time withstand current 4 mm²0.48 kA
Short-time withstand current 6 mm²0.72 kA
ResultTest passed
Power-frequency withstand voltage
Test voltage setpoint2.2 kV
ResultTest passed
Mechanical properties
Mechanical data
Open side panelYes
Mechanical tests
Mechanical strength
ResultTest passed
Attachment on the carrier
DIN rail/fixing supportNS 35
Test force setpoint1 N
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
4 mm² / 0.9 kg
6 mm² / 1.4 kg
ResultTest passed
Environmental and real-life conditions
Needle-flame test
Time of exposure30 s
ResultTest passed
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
SpectrumService life test category 1, class B, body mounted
Frequencyf1 = 5 Hz to f2 = 150 Hz
ASD level1.857 (m/s²)²/Hz
Acceleration0.8g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
Pulse shapeHalf-sine
Acceleration5g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (storage/transport)30 % ... 70 %
Standards and regulations
Connection in acc. with standardIEC 60947-7-1
Mounting
Mounting typeNS 35/7,5
NS 35/15

Returns

In order for the Goods to be eligible for a return, please make sure that:

The Goods were purchased in the last 14 days
The Goods are in the original packaging
The Goods were not used or damaged