Phoenix PSU TRIO-PS-2G/1AC/24DC/5

3 In stock
SKU
2903148
Quick Overview
Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 1-phase, output: 24 V DC/5 A
€151.31 €123.02

Shipping Information

Free Shipping - On Orders Over €150.

Money Back Guarantee.

Ships Items Quickly.

Input data
AC operation
Network typeStar network
Nominal input voltage range100 V AC ... 240 V AC
Input voltage range100 V AC ... 240 V AC -15 % ... +10 %
Input voltage range AC85 V AC ... 264 V AC
Electric strength, max.≤ 300 V AC 15 s
Typical national grid voltage120 V AC
230 V AC
Voltage type of supply voltageAC/DC
Inrush current≤ 16 A (typical)
Inrush current integral (I2t)< 0.6 A2s
Inrush current limitationtyp. 16 A (after 1 ms)
AC frequency range50 Hz ... 60 Hz ±10 %
Mains buffering timetyp. 20 ms (120 V AC)
typ. 100 ms (230 V AC)
Current consumption2.2 A (100 V AC)
1.9 A (120 V AC)
1.1 A (230 V AC)
1.1 A (240 V AC)
Nominal power consumption272 VA
Protective circuitTransient surge protection; Varistor
Power factor (cos phi)0.5
Typical response time< 1 s
Input fuse6.3 A (internal (device protection))
Recommended breaker for input protection6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE< 0.25 mA
DC operation
Nominal input voltage range110 V DC ... 250 V DC
Input voltage range99 V DC ... 275 V DC
Switch-on voltage≥ 88 V DC
Shut-down voltage< 60 V DC
Voltage type of supply voltageAC/DC
Mains buffering time> 100 ms (230 V AC)
Current consumption1.4 A (110 V DC)
0.6 A (250 V DC)
Output data
Efficiency> 90 % (for 230 V AC and nominal values)
Output characteristicU/I with dynamic load reserve
Nominal output voltage24 V DC ±1 %
Setting range of the output voltage (USet)24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)5 A
Dynamic Boost (IDyn.Boost)7.5 A (5 s)
Derating> 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 30 V DC
Control deviation< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple< 50 mVPP (with nominal values)
Output power120 W
180 W
Maximum no-load power dissipation< 1 W
Power loss nominal load max.< 16 W
Rise time≤ 12 ms (UOUT (10 % ... 90 %))
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes
Signal: DC OK
Maximum switching voltage30 V AC/DC
Continuous load current100 mA
Connection data
Input
Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length10 mm
Output
Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length8 mm
Signal
Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm
LED signaling
Types of signalingLED
Floating signal contact
Signal output: LED status indicator
Signalization designationDC OK
Status display“DC OK” LED
Colorgreen
Electrical properties
Number of phases1.00
Insulation voltage input/output3 kV AC (type test)
1.5 kV AC (routine test)
Product properties
Product typePower supply
MTBF (IEC 61709, SN 29500)> 3380000 h (25 °C)
> 1970000 h (40 °C)
> 900000 h (60 °C)
Insulation characteristics
Protection classII (in closed control cabinet)
Degree of pollution2
Dimensions
Width35 mm
Height130 mm
Depth115 mm
Installation dimensions
Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm
Mounting
Mounting typeDIN rail mounting
Assembly instructionsalignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Mounting positionhorizontal DIN rail NS 35, EN 60715
With protective coatingNo
Material specifications
Inflammability class in acc. with UL 94 (housing / terminal blocks)V0
Housing materialPlastic
Type of housingPolycarbonate
Hood versionPolycarbonate
Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.
Standards and regulations
Rail applicationsEN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyIEC 62368-1 (SELV)
Standard – Safety extra-low voltageIEC 62368-1 (SELV) und EN 60204-1 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Standard - Safety of transformersEN 61558-2-16 (air clearances and creepage distances only)
Approval data
UL approvalsUL Listed UL 508
UL/C-UL Recognized UL 60950-1
Conformity/Approvals
SIL in accordance with IEC 615080
EMC data
Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
EMC requirements for noise emissionEN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EN 61000-6-2
Noise emissionEN 55011 (EN 55022)
Noise immunityEN 61000-6-2:2005
Electrostatic discharge
Standards/regulationsEN 61000-4-2
Electrostatic discharge
Contact discharge6 kV (Test Level 4)
Discharge in air8 kV (Test Level 4)
CommentsCriterion A
Electromagnetic HF field
Standards/regulationsEN 61000-4-3
Electromagnetic HF field
Frequency range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency range1 GHz ... 2 GHz
Test field strength10 V/m (Test Level 3)
Frequency range2 GHz ... 3 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A
Fast transients (burst)
Standards/regulationsEN 61000-4-4
Fast transients (burst)
Input4 kV (Test Level 4 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Signal1 kV (Test Level 2 - asymmetrical)
CommentsCriterion A
Surge voltage load (surge)
Standards/regulationsEN 61000-4-5
Input3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal1 kV (Test Level 2 - asymmetrical)
CommentsCriterion B
Conducted interference
Standards/regulationsEN 61000-4-6
Conducted interference
Input/Outputasymmetrical
Frequency range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)
Emitted interference
Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.

Returns

In order for the Goods to be eligible for a return, please make sure that:

The Goods were purchased in the last 14 days
The Goods are in the original packaging
The Goods were not used or damaged