18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulations
Overvoltage category
EN 61010-1
II (≤ 4000 m)
Overvoltage category
EN 62477-1
III (≤ 2000 m)
Electrical safety
Standards/specifications
IEC 61010-1 (SELV)
Electrical safety
Standards/specifications
IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Electrical safety
Standards/specifications
IEC 61558-2-16
Electrical safety
Standards/specifications
EN 61204-3
Electrical safety
Standards/specifications
IEC 61010-1
Electrical safety
Standards/specifications
DIN EN 60335-1
Approval data
UL
Identification
UL 1310 Class 2 Power Units
UL
Identification
UL/C-UL Listed UL 61010-1
UL
Identification
UL/C-UL Listed UL 61010-2-201
UL
Identification
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC data
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Conducted noise emission
EN 55016
EN 61000-6-3 (Class B)
Interference emission
Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission
EN 55016
EN 61000-6-3 (Class B)
Noise immunity
EN 61000-6-2:2005
Harmonic currents
Standards/regulations
EN 61000-3-2
EN 61000-3-2 (Class A)
Flicker
Standards/regulations
EN 61000-3-3
Frequency range
0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
asymmetrical 4 kV (Test Level 4)
Output
asymmetrical 2 kV (Test Level 3)
Comments
Criterion A
Surge voltage load (surge)
Standards/regulations
EN 61000-4-5
Input
symmetrical 2 kV (Test Level 4)
asymmetrical 4 kV (Test Level 4)
Output
symmetrical 1 kV (Test Level 3)
asymmetrical 2 kV (Test Level 3)
Comments
Criterion A
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
Input/Output
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Voltage dips
Standards/regulations
EN 61000-4-11
Voltage
230 V AC
Frequency
50 Hz
Voltage dip
70 %
Number of periods
25 periods
Additional text
Class 3
Comments
Criterion A
Voltage dip
40 %
Number of periods
10 periods
Additional text
Class 3
Comments
Criterion A
Voltage dip
0 %
Number of periods
1 period
Additional text
Class 3
Comments
Criterion A
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.