Phoenix PTFIX 6/18X2,5-NS35A GY

6 In stock
SKU
3273242
Quick Overview
Distribution block, the blocks can be bridged with one another via the conductor shaft, for corresponding plug-in bridges, see accessories, Block with horizontal alignment and integrated supply, nom. voltage: 690 V, nominal current: 24 A, connection method: Push-in connection, Load contact, cross section: 0.14 mm2 - 4 mm2, Push-in connection, Line contact, Rated cross section: 6 mm2, cross section: 0.5 mm2 - 10 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray
€5.72 €4.65

Shipping Information

Free Shipping - On Orders Over €150.

Money Back Guarantee.

Ships Items Quickly.

Notes
Notes on operationthe blocks can be bridged with one another via the conductor shaft, for corresponding plug-in bridges, see accessories
General
NoteThe maximum load current of a single clamping unit must not be exceeded.
For power distribution applications, IEC 60364-4-43.2008; modified + corrigendum Okt. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff must be observed!
Product properties
Product typeDistributor terminal block
Number of connections19
Number of rows1
Potentials1
Insulation characteristics
Overvoltage categoryIII
Degree of pollution3
Electrical properties
Rated surge voltage8 kV
Maximum power dissipation for nominal condition0.77 W
Connection data
Service Entranceyes
Number of connections per level19
Nominal cross section2.5 mm²
Rated cross section AWG14
Load contact
Stripping length8 mm ... 10 mm
Internal cylindrical gageA3
Conductor cross section solid0.14 mm² ... 4 mm²
Cross section AWG26 ... 12
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]26 ... 14
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)0.14 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 2.5 mm²
Nominal current24 A
Maximum load current32 A (with 4 mm² conductor cross section)
Maximum total current57 A (with 10 mm² conductor cross section)
Nominal voltage690 V
Line contact
Stripping length10 mm ... 12 mm
Conductor cross section solid0.5 mm² ... 10 mm²
Cross section AWG20 ... 8
Conductor cross section flexible0.5 mm² ... 10 mm²
Conductor cross section, flexible [AWG]20 ... 10
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)0.5 mm² ... 6 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 6 mm²
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve)0.5 mm² ... 1.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1.5 mm²
Nominal current41 A (with 6 mm² conductor cross section)
Maximum load current57 A (with 10 mm² conductor cross section)
Nominal cross section6 mm²
Load contact Connection cross sections directly pluggable
Conductor cross section solid0.34 mm² ... 4 mm²
Conductor cross section, solid [AWG]24 ... 12
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)0.34 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.34 mm² ... 2.5 mm²
Line contact Connection cross sections directly pluggable
Conductor cross section solid1 mm² ... 10 mm²
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)1 mm² ... 6 mm²
Flexible conductor cross section (ferrule with plastic sleeve)1 mm² ... 6 mm²
Dimensions
Width56.5 mm
Height NS 35/7,530.9 mm
Length45.7 mm
Material specifications
Colorgray
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Electrical tests
Surge voltage test
Test voltage setpoint9.8 kV
ResultTest passed
Temperature-rise test
Requirement temperature-rise testIncrease in temperature ≤ 45 K
ResultTest passed
Short-time withstand current 6 mm²0.72 kA
Short-time withstand current 10 mm²1.2 kA
ResultTest passed
Power-frequency withstand voltage
Test voltage setpoint1.89 kV
ResultTest passed
Mechanical properties
Mechanical data
Open side panelNo
Mechanical tests
Mechanical strength
ResultTest passed
Attachment on the carrier
DIN rail/fixing supportNS 35
Test force setpoint5 N
ResultTest passed
NoteWhen aligning several blocks, it is recommended to either place a DIN rail adapter underneath the connection point or a flange element between the blocks.
For versions with 6 or 7 connections, it is enough to place one DIN rail adapter centrally per block and place flange elements after every other block.
When using the DIN rail adapter PTFIX-NS35, an aligned block must not protrude by more than a half.
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.5 mm² / 0.3 kg
6 mm² / 1.4 kg
10 mm² / 2 kg
ResultTest passed
Test for conductor damage and slackening
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
ResultTest passed
Environmental and real-life conditions
Aging
Temperature cycles192
ResultTest passed
Needle-flame test
Time of exposure30 s
ResultTest passed
Oscillation/broadband noise
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
SpectrumService life test category 2, bogie-mounted
Frequencyf1 = 5 Hz to f2 = 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
ResultTest passed
Shocks
SpecificationDIN EN 50155 (VDE 0115-200):2008-03
Pulse shapeHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
ResultTest passed
Ambient conditions
Ambient temperature (operation)-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C
Permissible humidity (storage/transport)30 % ... 70 %
Standards and regulations
Connection in acc. with standardIEC 60947-7-1
IEC 60947-7-1
IEC 60947-7-1
IEC 60947-7-1
Mounting
Mounting typeNS 35/7,5
NS 35/15

Returns

In order for the Goods to be eligible for a return, please make sure that:

The Goods were purchased in the last 14 days
The Goods are in the original packaging
The Goods were not used or damaged